SSTS Permitting
Compliance Inspection Compliance Inspection Compliance Inspection # CI-2021-2778, Submission # Submission-2021-2980, UID # 35581
Status: Compliance Inspection Accepted
Status: Compliance Inspection Accepted
System Status
System status on date: | 08/16/2021 | System Status: | Compliant |
Property Information
Property Information: | |||||||||||||||||
Owner's representative: |
|
Impact on Public Health
System discharges sewage to the ground surface: |
No | System discharges sewage to drain tile or surface waters: |
No | System causes sewage backup into dwelling or establishment: |
No |
Verification method(s): | Other methods not listed (See Comments/Explanation) |
Comments/Explanation: | Visual Inspection of the area. No signs of sewage to the ground. The owner did not report back-ups into the house. |
Tank Integrity
System consists of seepage pit, cesspool, drywell, or leaching pit: |
No |
Sewage tank(s) leak below their designed operating depth: |
No |
Verification method(s): | Other methods not listed (See Comments/Explanation) |
Comments/Explanation: | Tanks pumped and visually inspected with camera. No signs of cracks or leaking in any of the tanks. |
Other Compliance Conditions
Maintenance hole covers are damaged, cracked, unsecured, or appear to be structurally unsound: |
No |
Other issues (electrical hazards, etc.) to immediately and adversely impact public health or safety: |
No |
System is non protective of groundwater for other conditions as determined by the inspector: |
No |
Explain: | Tanks and area around tanks inspected. |
Date of Install
Date of install known: | Yes |
Date of installation: | 01/01/1986 |
Soil Separation
Shoreland/Wellhead Protection/Food, beverage, lodging? | Yes |
Drainfield has at least a two-foot vertical separation distance from periodically saturated soil or bedrock: |
No |
Drainfield meets the designed vertical separation distance from periodically saturated soil or bedrock.: |
No |
Verification method(s): | Conducted soil observation(s) (Attach boring logs) |
A. Bottom of distribution media: | 3 Decimal Feet |
B. Periodically saturated soil/bedrock: | 7 Decimal Feet |
C. System separation: | 4 Decimal Feet |
D. Required compliance separation: | 2.6 Decimal Feet |
Operating Permit and Nitrogen BMP
Is system operating under an Operating Permit: | No |
Is the system required to employ Nitrogen BMP: | No |
Comments and File Attachments
Comments or recommendations: | See attached soil boring log & site map |
Attach Files: |
Certification
Inspector: |
Please search for and choose SELF/OTHER if what you need does not appear in the list
|
Inspector Contact (If 'self/other' is selected from the Inspector Lookup): | Jesse Kloeppner |
Inspector Email Address: | jesse@ksd-mn.com |
Terms
Certification
By submitting this form I hereby certify that all the necessary information has been gathered to determine the compliance status of this system. No determination of the future
system performance has been nor can be made due to unknown conditions during system construction, possible abuse of the system, inadequate
maintenance, or future water usage
Invoice #7220 (08/17/2021)
Charge | Cost | Quantity | Total |
---|---|---|---|
added 08/17/2021 2:53 PM $47 Flat Fee |
$42.00 | x 1 | $42.00 |
Grand Total | |||
Total | $42.00 | ||
Payment 08/17/2021 | $42.00 | ||
Due | $0.00 |
Action: Print
Approvals
Approval | Signature | Options |
---|---|---|
Applicant | Jesse J. Kloeppner - 08/17/2021 2:53 PM cd7e3e54fe091bcf16319c0de721dd4f e7ad5dcea28b8a1d8f554e85509e3094 | |
#1 Compliance Inspection Accepted | Sarah Borrell - 09/03/2021 11:24 AM 5b071dfd75fe59609626b6cbe0156e0e 37670a6f3e60ca6406735477a39b7fc5 |
Inspection has been approved. All signatures have been obtained.
Text: | |
File(s): |
Text: | |
File(s): |
Compliance Letter Type: | Certificate of Compliance | Who's signature should be on the letter? | Sarah Borrell | Permit number to reference in "No Replace" letter: | |
Was the letter sent? | Yes | Compliant/Non-Compliant: | Compliant |
Certificate of Compliance: |
Letter of Non-Compliance: |