Compliance Inspection Compliance Inspection Compliance Inspection # CI-2022-2980, Submission # Submission-2021-3167, UID # 38314
Status: Compliance Inspection Accepted
Status: Compliance Inspection Accepted
System Status
System status on date: | 11/28/2021 | System Status: | Compliant |
Property Information
Property Information: | |||||||||||||||||
Owner's representative: |
|
Impact on Public Health
System discharges sewage to the ground surface: |
No | System discharges sewage to drain tile or surface waters: |
No | System causes sewage backup into dwelling or establishment: |
No |
Verification method(s): | Searched for surface outlet Searched for seeping in yard/backup into home |
Tank Integrity
System consists of seepage pit, cesspool, drywell, or leaching pit: |
No |
Sewage tank(s) leak below their designed operating depth: |
No |
Verification method(s): | Examined empty (pumped) tank(s) |
Comments/Explanation: | repumped and repaired inlet to old tank. It's precast water tight |
Other Compliance Conditions
Maintenance hole covers are damaged, cracked, unsecured, or appear to be structurally unsound: |
No |
Other issues (electrical hazards, etc.) to immediately and adversely impact public health or safety: |
No |
System is non protective of groundwater for other conditions as determined by the inspector: |
No |
Date of Install
Date of install known: | Yes |
Date of installation: | 06/01/1976 |
Soil Separation
Shoreland/Wellhead Protection/Food, beverage, lodging? | No |
Drainfield has at least a two-foot vertical separation distance from periodically saturated soil or bedrock: |
Yes |
Drainfield meets the designed vertical separation distance from periodically saturated soil or bedrock.: |
Yes |
Verification method(s): | Conducted soil observation(s) (Attach boring logs) |
A. Bottom of distribution media: | 2 Decimal Feet |
B. Periodically saturated soil/bedrock: | 5 Decimal Feet |
C. System separation: | 3 Decimal Feet |
D. Required compliance separation: | 2 Decimal Feet |
Operating Permit and Nitrogen BMP
Is system operating under an Operating Permit: | No |
Is the system required to employ Nitrogen BMP: | No |
Comments and File Attachments
Attach Files: |
|
Certification
Inspector: |
Please search for and choose SELF/OTHER if what you need does not appear in the list
|
Inspector Email Address: | sssepticsolutions@gmail.com |
Terms
Certification
By submitting this form I hereby certify that all the necessary information has been gathered to determine the compliance status of this system. No determination of the future
system performance has been nor can be made due to unknown conditions during system construction, possible abuse of the system, inadequate
maintenance, or future water usage
Invoice #7657 (12/21/2021)
Charge | Cost | Quantity | Total |
---|---|---|---|
added 12/21/2021 4:23 PM $47 Flat Fee |
$42.00 | x 1 | $42.00 |
Grand Total | |||
Total | $42.00 | ||
Payment 12/21/2021 | $42.00 | ||
Due | $0.00 |
Action: Print
Approvals
Approval | Signature | Options |
---|---|---|
Applicant | Shelley L. Schlomka - 01/26/2022 3:50 PM c3a39625bdc352e8c72fe1f0ac39072c 23c992296b9ba00d83f3fab182db4c55 | |
#1 Compliance Inspection Accepted | Sarah Borrell - 01/28/2022 3:21 PM 022b427cc5708c70b19faf7a07799b68 da2e141c331ba12ddaad97e45f2e32ea |
Inspection has been approved. All signatures have been obtained.
Text: | |
File(s): |
|
Text: | System #1 (west of home). From inspector on 1/26/22 prior to amending report: Tank #1 - Tank is watertight. I rechecked on 11/28/21 but I need to update the date on the report. Inlet of the tank fixed. All dirt sucked out of the bottom. Backflushed the tank to ensure no cracks. |
File(s): |
Compliance Letter Type: | Certificate of Compliance | Who's signature should be on the letter? | Sarah Borrell | Permit number to reference in "No Replace" letter: | |
Was the letter sent? | Yes | Compliant/Non-Compliant: | Compliant |
Certificate of Compliance: |
Letter of Non-Compliance: |